Click to enlarge image
|
CAST IRON CHILLER
- HIGH RELIANCE
By ISO9001 Quality System, As whole the progress of the work are produced by process control system, the high quality is guaranteed.
- Excellent durability:
Long-life and rugged compressor ensures long and safe use.
- CONTROL BOX
By designed for th ergo-mechanics, the position of the control box and layouts are convenience for check and operation.
- COMPLETE AUTOMATIC SYSTEM
Happened a high-pressure alarm, over current, lack of cold-water, and unusual cooler, light up the alarm, the user can identify easily something wrong or not. |
| Proportional Control Function |
- Accurate temperature control is realized through use of PID (proportional integral differential) control method. (Dramatical reduction of energy expenses)
- Indication of abnormal areas and warning system are provided.
- Maximum discharge capacity and maximum discharge pressure are achieved through miniature power pump.
- Highly accurate temperature controls are realized in temperature deviation(△± 0.5°C).
- 24-hours operation at the initial temperature is available through a thermostat.
- Controls by a thermostat depending on loads ensures economical effects in operational expenses.
- All manipulations are available through one touch in the control panel, which provides digital temperature setting and indication. Lighting and warning alarm in the abnormal areas are available.
|
| DAEIL CONTROL SYSTEM ADVANTAGE |
- The control system, development and manufactured only DAEIL Technology.
- By designed for the ergo-mechanics, from eye heig ht, you can grasp the running condition at sight.
- Simple display parts, be able to exactly supervise, understanding functions easily, by graphic mark.
- By a digital control method, we give the accuracy information more and more quickly.
- Convenience functions, happened something wrong, by oneself, indicate the alarm sign.
|
DRC SERIES
|
|
DRC-020 |
DRC-030 |
DRC-050 |
DRC-075 |
|
Cooling Capacity (kcal/h) |
5,000kcal/h |
7,500kcal/h |
12,500kcal/h |
18,750kcal/h |
|
Working Temp. |
5 °C ~ 30 °C |
|
Media |
Fresh Water |
|
Refrigerant |
R-22 (HCFC22) |
|
Power consumption(kw) |
2.8 |
3.8 |
6.6 |
9.1 |
|
Power Source |
220V-1P-60Hz / 220V 380V 440V -3P-60Hz |
|
Compressor |
2HP(1.5KW) |
3HP(2.25KW) |
5HP(3.75KW) |
7.5HP(5.25KW) |
|
Condenser Fan |
Φ 350 x 2EA |
Φ 400 x 2EA |
Φ 450 x 2EA |
|
Safety Devices |
Water Temp. Sensor, Water Pressure Gauge, Flow Switch, Dual Pressure S/W, OCR, and Oil Pressure S/W are available as an option for models. |
|
Abnormal Alarm |
Temperature Sensor, High Temp., Low Temp., Power, Ref.HP. Ref.LP, Compressor, Subcooling, Pump and Oil Pressure S/W are available as an option for models. |
|
Pump Flow Rate(I/min@2bar) |
20~40 |
30~60 |
50~66 |
75~140 |
|
Tank Capacity(I) |
45 |
45 |
240 |
240 |
|
Inlet/Outlet Connection |
1" |
1" |
1" |
1-1/2" |
|
Dimension (W x D x H) |
790mm x 535mm x 1110mm |
860mm x 750mm x 1300mm |
|
DRC-100 |
DCC-150 |
DCC-200 |
DCC-300 |
|
25,000kcal/h |
37,500kcal/h |
50,000kcal/h |
75,000kcal/h |
|
5 °C ~ 30 °C |
|
Fresh Water |
|
R-22 (HCFC22) |
|
11.1 |
16.5 |
22.2 |
32.2 |
|
220V-1P-60Hz / 220V 380V 440V -3P-60Hz |
|
10HP(7.55KW) |
15HP(11.25KW) |
20HP(15KW) |
30HP(22.5KW) |
|
Φ 550 x 2EA |
Φ 600 x 2EA |
Φ 600 x 3EA |
Φ 700 x 3EA |
|
Water Temp. Sensor, Water Pressure Gauge, Flow Switch, Dual Pressure S/W, OCR, and Oil Pressure S/W are available as an option for models. |
|
Temperature Sensor, High Temp., Low Temp., Power, Ref.HP. Ref.LP, Compressor, Subcooling, Pump and Oil Pressure S/W are available as an option for models. |
|
100~140 |
150~200 |
200~500 |
300~500 |
|
420 |
510 |
700 |
1400 |
|
1-1/2" |
2" |
2" |
2" |
|
1276mm x 680mm x 1600mm |
1646mm x 680mm x 1845mm |
1846mm x 855mm x 1845mm |
|
|
|
|
| |
|
|
|